Honeywell Ventilation Hood D896 User Manual

D896 Automatic Vent Damper  
PRODUCT DATA  
FEATURES  
4-wire plug receptacle.  
Includes wiring harness on select models to fit plug  
receptacle onto S86/S8600/S8610/S8620 /L7148/L8148  
or Penn Baso G60 or G66.  
For use only on atmospheric type gas-fired furnaces  
and boilers equipped with draft hoods.  
Applicable to direct spark ignition (DSI), intermittent  
pilot (IP), hot surface ignition (HSI), and standing pilot  
systems.  
Ambient temperature range 32°F (0°C) to 150°F (65°C).  
Requires dual automatic combination gas control  
valve or two separate single function main gas valves.  
Interlock switch provides safe operation; burner fires  
only with damper in open position.  
GENERAL  
24V operation for easy, low-cost wiring.  
Visual indicator shows damper position.  
D896 Automatic Vent Dampers are used with atmospheric  
type, gas-fired equipment to reduce home heating losses by  
closing off the vent between heat cycles.  
30-second nominal closing time for optimum energy  
savings.  
Quiet motor and relay.  
Wiring harnesses available separately to fit a variety of  
applications.  
Contents  
General ...............................................................................  
Features ..............................................................................  
Specifications ......................................................................  
Ordering Information ...........................................................  
Application...........................................................................  
Installation ...........................................................................  
Settings ...............................................................................  
Operation and Checkout .....................................................  
Troubleshooting ...................................................................  
Instructions to the Homeowner ...........................................  
1
1
2
2
3
4
7
7
8
9
ANSI Standards .................................................................. 10  
® U.S. Registered Trademark  
Copyright © 1997 Honeywell Inc.  
68-0186  
All Rights Reserved  
 
D896 AUTOMATIC VENT DAMPER  
NOTE: A minimum of a 30 VA transformer must be used  
when D896 is installed with S86/S8600/S8610/  
S8620.  
Approvals:  
American Gas Association Certified:  
Certificate No. U-66-2A1.  
Canadian Gas Association Design Certified:  
1029AVD-9081.  
Electrical Connections:  
Four-wire plug receptacle.  
Replacement Parts:  
Thermostat Anticipator Setting:  
0.13A.  
Damper Actuator is field replaceable without removing the  
damper assembly from the stack.  
197516A Wiring Harness is a 4-wire cable, 8 feet (2.5  
meters) long, with D896 mating plug on one end and  
mating plug for S86/S8600/S8610/S8620 or Penn Baso  
G60 or G66 on the other. An outlet box connector is on  
each end.  
Operating Times:  
Approximate Damper Opening Time: 30 seconds.  
Approximate Damper Closing Time: 30 seconds.  
Temperature Ratings:  
Minimum Ambient: 32°F (0°C).  
Maximum Ambient: 150°F (66°C).  
Maximum Furnace Stack: 575°F (302°C).  
Shipping: -20°F to +120°F (-29°C to +49°C).  
APPLICATION  
The D896 Automatic Vent Damper is a 24 Vac, motorized  
stack damper. The damper closes off the furnace or boiler  
stack during the heating off-cycle. Use the D896 only on  
Underwriters Laboratories Inc. listed and American Gas  
Association design certified atmospheric type, gas-fired  
furnaces and boilers. The furnaces or boilers must be  
equipped with a draft hood that has an outlet area no larger  
than the damper inlet area. Do not use with oil-fired furnace  
or boiler, power burner, or direct vent furnace or boiler.  
Mounting: See Fig. 2.  
Vertical Stack: Any orientation.  
Horizontal Stack: The damper actuator must be on the left  
or right side of the vent.  
IMPORTANT  
Do not mount the vent damper with the actuator  
above or below the vent.  
Dimensions:  
See Fig. 1.  
DIM. F  
DIM. E  
DIA  
A
DIA  
C
DIA  
B
DIM.  
G
1
4
1
(32)  
DIM.  
H
3
4
2
(70)  
9
16  
DIM.  
D
4
(116)  
7
8
7/8 DIA. STD. KNOCKOUT (3)  
(ONE, OPPOSITE SIDE)  
3
(98)  
DIA. A  
in. (mm)  
DIA. B  
in. (mm)  
DIA. C  
in. (mm)  
DIM. D  
in. (mm)  
DIM. E  
in. (mm)  
DIM. F  
in. (mm)  
DIM. G  
in. (mm)  
DIM. H  
in. (mm)  
BODY SIZE  
(REF)  
4 (102)  
5 (127)  
6 (152)  
7 (178)  
8 (203)  
9 (229)  
10 (254)  
11 (279)  
12 (305)  
4 1/16 (103)  
5 1/16 (129)  
6 1/16 (154)  
7 1/16 (179)  
8 1/16 (205)  
9 1/16 (230)  
1 9/16 (40)  
1 9/16 (40)  
1 9/16 (40)  
3 3/16 (81)  
3 3/16 (81)  
3 3/16 (81)  
4 1/2 (114)  
4 1/2 (114)  
4 1/2 (114)  
7 1/2 (191)  
7 1/2 (191)  
7 1/2 (191)  
11 1/2 (292)  
11 1/2 (292)  
11 1/2 (292)  
6 (152)  
6 (152)  
6 (152)  
9 (229)  
9 (229)  
9 (229)  
13 (330)  
13 (330)  
13 (330)  
6 3/4 (171)  
7 1/4 (184)  
8 7/8 (225)  
9 7/8 (251)  
4 (102)  
5 (127)  
6 (152)  
7 (178)  
8 (203)  
9 (229)  
10 (254)  
11 (279)  
12 (305)  
3 15/16 (100)  
4 15/16 (125)  
5 15/16 (151)  
6 15/16 (176)  
7 15/16 (202)  
8 15/16 (224)  
9 15/16 (252)  
10 15/16 (278)  
11 15/16 (303)  
7 3/4 (197) 10 7/8 (276)  
8 1/4 (209) 11 7/8 (301)  
8 3/4 (222) 12 7/8 (327)  
9 1/4 (235) 13 7/8 (352)  
9 3/4 (248) 14 7/8 (378)  
10 1/4 (260) 15 7/8 (403)  
10 3/4 (274) 16 7/8 (428)  
M11381  
10 1/16 (256) 5 3/16 (132)  
11 1/16 (281) 5 3/16 (132)  
12 1/16 (306) 5 3/16 (132)  
Fig. 1. Installation dimensions in in. (mm).  
3
68-0186  
 
D896 AUTOMATIC VENT DAMPER  
IMPORTANT  
Location  
1. The atmospheric draft hood outlet area must be  
smaller or equal to the inlet area of the damper  
assembly.  
2. If a second gas valve needs to be installed, refer  
to the gas valve manufacturer instructions for the  
procedure.  
3. Using a dual automatic valve combination gas  
control or two separate gas valves is required  
with the D896.  
4. Do not use with L8148 or L8124 with manual/  
automatic switch because the switch can override  
the safety interlock in the system wiring and  
cause a hazardous condition.  
The D896 must be installed after the furnace or boiler draft  
hood. See Fig. 2. Make sure the D896 Motor Actuator is  
readily visible and accessible. The damper must be located  
where air can freely circulate around it.  
WARNING: DO NOT INSTALL THE  
VENT DAMPER WITHIN 6 IN. (152 mm)  
OF COMBUSTIBLE MATERIAL.  
NO  
D896 MOTOR  
ACTUATOR  
VENT PIPE  
CURVE  
2
5. Do not install on an appliance equipped with an  
automatic valve with a manual opener unless the  
manual opener is rendered inoperative or the  
automatic valve is replaced with an automatic  
valve without a manual opener.  
DRAFT  
HOOD  
1
6. On retrofit applications, installation identification  
label (provided) must be filled out by installer and  
applied to outside of cover.  
CHIMNEY  
3
INSTALLATION  
When Installing this Product…  
FURNACE OR BOILER  
1. Read these instructions carefully. Failure to follow them  
could cause a hazardous condition.  
WATER HEATER  
1
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE  
APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY  
INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION  
OR CARBON MONOXIDE POISONING, COULD RESULT.  
2. Check the ratings given in the instructions and on the  
product to make sure the product is suitable for your  
application.  
3. Installer must be a trained experienced service  
technician. The D896 must be installed in compliance  
with local codes or the Natural Gas Installation Code  
CAN/CGA-B149.1-B149.1-M91 and CSA C22.2 #3  
Electrical Features of Fuel Burning Equipment, or the  
National Fuel Gas Code (ANSI Z223.1—NFPA 54) and  
the National Electrical Codes (ANSI C1—NFPA70). Use  
the ANSI Standard Z21.66-1994 included at the end of  
this specification during installation.  
DO NOT INSTALL THE VENT DAMPER ON VENT PIPE CURVE.  
2
3
DO NOT RUN WIRES NEAR HIGH TEMPERATURE SURFACES.  
USE STAND-OFF BRACKETS IF NECESSARY.  
M11370  
Fig. 2. D896 location.  
Do not install the D896:  
— Where the stack temperature is higher than 575°F (284°C).  
— Where the ambient temperature is higher than 150°F  
(66°C).  
— In small or enclosed spaces where temperature can  
exceed 150° F (66°C). See WARNING following.  
— On the vent pipe curve. See Fig. 2.  
NOTE: In Canada, the damper is not certified for  
retrofit application. Certification for the  
suitability of the damper and appliance  
combination must be determined by the  
Canadian Gas Association.  
WARNING  
4. Install only on an appliance connected to a factory built  
chimney or vent that complies with a recognized  
standard, or to a masonry or concrete chimney that is  
lined with a material acceptable to local code.  
5. After installation is complete, check out product  
operation as provided in the Checkout section. See  
Exhibits A and B at the end of this specification.  
Severe illness or death possible. Prevent  
explosion or carbon monoxide poisoning.  
Overheating can cause premature device failure. Be  
sure the D896 is used to control only one appliance.  
Mounting  
The damper must be mounted as close as possible to the  
draft hood without modifying the draft hood. The D896 can be  
mounted vertically or horizontally. When vertically mounting  
the vent damper, the motor actuator can be in any position.  
See Fig. 3.  
CAUTION  
Can cause electrical shock or equipment damage.  
1. Disconnect power supply.  
2. Do not install within 6 in. (152 mm) of combustible  
materials.  
3. Do not negate the action of any existing safety or  
operational control.  
Horizontal mounting requires the actuator to be located within  
45 degrees directly above or directly below the horizontal  
diameter of the stack pipe. See Fig. 2 and 3.  
68-0186  
4
 
D896 AUTOMATIC VENT DAMPER  
HORIZONTAL VENT INSTALLATION  
D896  
NO  
NO  
YES  
YES  
TO CHIMNEY  
FLOW  
FROM FURNACE  
OR BOILER  
INSTALL VENT DAMPER  
ONLY WITH ACTUATOR  
TO SIDES OF VENT.  
DO NOT MOUNT VENT  
DAMPER WITH  
ACTUATOR ABOVE  
OR BELOW THE VENT.  
VERTICAL VENT INSTALLATION  
TO  
CHIMNEY  
MOTOR  
ACTUATOR  
INSTALL VENT  
DAMPER WITH  
ACTUATOR IN  
ANY POSITION.  
D896  
FLOW  
DAMPER  
BLADE PLUG  
DAMPER  
BLADE  
FROM FURNACE  
OR BOILER  
M11371  
FOR DSI AND IP INSTALLATIONS ONLY – PLACE PLUG ON HOLE:  
HOLD DAMPER BLADE AND PUSH DOWN ON PLUG.  
M9675  
Fig. 3. Installing D896 Vent Damper.  
Fig. 4. Installing damper blade plug.  
IMPORTANT  
Never mount the vent damper with the motor  
actuator above or below the vent.  
Wiring  
WARNING  
Do not install the damper blade plug if the vent damper is  
installed on a system with a continuous or standing pilot. The  
hole provides the minimum vent area required by code for  
safe operation.  
Severe illness or death possible. Prevent  
explosion or carbon monoxide poisoning.  
1. Use dual automatic valve combination gas  
controls or two separate single function main gas  
valves with the D896.  
2. Do not use the D896 with an L8148 or L8124 with  
a manual/automatic switch because the switch  
can override the safety interlocks in the system  
wiring and cause carbon monoxide buildup.  
Use the damper blade plug when the damper is installed on a  
system with either an intermittent pilot or direct ignition. The  
plug will increase system efficiency. See Fig. 4.  
To install the D896:  
1. Push the female end of the vent damper over the  
section of vent pipe coming from the furnace or boiler,  
but after the draft hood. Push the section of the vent  
pipe coming from the chimney over the male end of the  
vent damper.  
2. Secure the vent damper to the vent pipe with 1/2 in. (12  
mm) sheet metal screws. Use only the holes provided.  
3. Visually inspect the venting system for proper pitch.  
Pitch must comply with local codes or ANSI Z223.1—  
NFPA54.  
CAUTION  
1. Remove the shorting plug on the S8600, S8610  
or L8148E before attaching the wiring harness.  
2. Do not permit device wiring to contact high  
temperature surfaces.  
3. Label all wires prior to disconnecting when  
servicing controls. Wiring errors can cause  
explosion or carbon monoxide buildup.  
Important  
To install an additional gas valve:  
Do not operate the system with the D896 unplugged.  
Once the system has operated with the D896  
plugged into the S8600, S8610 or L8148E, the  
control module will not operate.  
1. Shut off the gas and electricity to the gas burner. (Use  
the manual shutoff valve in the supply line to the  
appliance.)  
2. Locate a position in the supply line between the  
appliance automatic gas valve and the burner.  
3. At the determined position, install an approved  
appropriately-sized, single-function automatic gas valve  
downstream from the existing automatic gas valve.  
Follow the valve manufacturer instructions for flow  
direction and position.  
D896 to L8148E, S8600F,H,M; S8610F,H  
Use the wiring harness included with the D896 to wire it  
according to the following instructions:  
1. Connect the molex plug to the D896 Harness Cable  
Connector. See Fig. 5.  
4. Restore the gas line supply and conduct a leak test on  
the gas piping and control system downstream from the  
appliance shutoff valve.  
2. Use Fig. 6 and 7 to connect the other end of the  
harness to the furnace, boiler or control module.  
3. Cycle system through at least two appliance operations.  
5
68-0186  
 
D896 AUTOMATIC VENT DAMPER  
D896  
Replacing D80B, D892 or Competitive  
Control with D896  
SERVICE  
SWITCH  
IGNITION GAS  
PWR LED  
NORM  
SERV  
WARNING  
Bodily harm and/or death possible. Prevent  
unsupervised gas flow.  
CALL FOR  
HEAT LED  
Improper wiring (device malfunction) of the D80B,  
D892, D896 or competitive devices can cause  
unsupervised gas flow.  
HARNESS  
CABLE  
CONNECTOR  
1
A wiring harness is included with most D896 models. Use the  
harness to wire the D896 according to the furnace or boiler  
manufacturer wiring instructions, if available; otherwise, follow  
these instructions. If field wiring is required, see appliance  
manufacturer instructions or see Fig. 8 for a typical wiring  
example. See Table 1 for competitive wiring cross reference.  
Always cycle system through at least two appliance  
operations.  
Table 1. Wiring Cross Reference.  
S3 SWITCH  
RELAY 1K  
1
USE STANDARD SCREWDRIVER TO MANUALLY OPEN AND  
CLOSE VENT DAMPER. PLACE SCREWDRIVER IN SLOTTED  
KNOB AND ROTATE COUNTERCLOCKWISE UNTIL  
Honeywell  
D892/D896  
Wires  
Honeywell  
Johnson  
EFFIKAL  
M11373  
D80B Wires Q35 Wires RVG Wires  
BOTH LEDS TURN ON.  
Fig. 5. D896 with cover off.  
Yellow  
Orange  
Blue  
Orange  
Blue and Red  
Black  
Green  
White  
Red  
1
2
3
4
Black  
Yellow  
Black  
24 Vac  
THERMOSTAT  
D896  
LED 2  
L8148E1166/L7148  
WIRING  
HARNESS  
4
4
4
T
W
Z
TV  
1K  
R1, R2, R3  
250 OHMS  
K1  
MOTOR  
6
2
2
NORMAL  
S4  
5
N.O.  
S3  
SERVICE  
3
FUSE  
N.C.  
C
N.O.  
2
N.C.  
S1  
C
K1  
1
3
N.O.  
N.C.  
5
S2  
C2  
L2  
C1  
L1  
C
LED 1  
3
1
1K1  
6-PRONG FEMALE MOLEX  
RECEPTACLE IN L8148E  
AND 5-PRONG MALE  
POLARIZED 4-PRONG MALE MOLEX PLUG AND  
4-PRONG FEMALE MATING PLUG ON CABLE  
B2  
B1  
CIRCULATOR  
MOLEX PLUG ON CABLE  
DAMPER OPEN  
DAMPER CLOSED  
SWITCHES AS SHOWN: S1,S2,S3  
L1  
(HOT)  
L2  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
1
AFTER D896 VENT DAMPER IS PLUGGED TO L8148E1166, FUSE  
BLOWS WHEN THERMOSTAT FIRST CLOSES. AFTER FUSE BLOWS,  
L8148E1166 OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.  
24V GND  
24V  
3
4
5
LED 1 LIGHTS WHEN DAMPER IS OPEN.  
LED 2 LIGHTS WITH CALL FOR HEAT.  
SERVICE SWITCH. THE NORMAL SWITCH SETTING IS NORM. IF THE  
SWITCH IS MOVED TO THE SERV POSITION, THE DAMPER REMAINS OPEN.  
6
NO W,Z TERMINALS ON L7148.  
M11382  
Fig. 6. Wiring diagram for D896 connection to L8148E1166 /L7148 using wiring harness with two Molex plugs.  
68-0186  
6
 
D896 AUTOMATIC VENT DAMPER  
S8600F, H, M; S8610F,H  
1
VENT  
2
GND  
(BURNER)  
24V  
GND  
DAMPER  
PLUG  
MV MV/PV PV  
24V TH-W  
SENSE  
SPARK  
WIRING  
HARNESS  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS  
AND OVERLOAD PROTECTION AS REQUIRED.  
D896  
VENT  
DAMPER  
REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE  
BLOWS ON STARTUP WHEN PLUG IS REMOVED;  
THEN MODULE OPERATES ONLY WHEN VENT  
DAMPER IS CONNECTED.  
M11375  
Fig. 7. Wiring diagram for D896 connection to S8600/S8610 using wiring harness with two Molex plugs.  
1. When replacing a D80B or D892 with a D896, use the  
included wire nuts to connect the D80B or D892 cable  
to the D896 cable. See Fig. 9.  
furnace or boiler burner lights. When the heating cycle ends,  
both LEDs turn off, the burner turns off and the damper  
automatically closes. Heating system efficiency is increased  
because the closed damper reduces the loss of residual  
appliance heat and heated room air through the draft diverter.  
a. Remove the black wire from the D80B (or D892)  
terminal 1.  
b. Use a wire nut to connect the D80B (or D892)  
black wire to the D896 blue wire.  
c. Remove the orange wire from the D80B (or  
D892) terminal 2.  
D896  
4
3
2
1
d. Wire nut the D80B (or D892) orange wire to the  
D896 yellow wire.  
e. Remove the red wire from the D80B (or D892)  
terminal 3 and the blue wire from the D80B (or  
D892) terminal 5.  
2
WIRING  
HARNESS  
f. Wire nut the D80B (or D892) red and blue wires  
to the D896 orange wire.  
g. Remove the yellow wire from the D80B (or D892)  
terminal 4.  
h. Wire nut the D80B (or D892) yellow wire to the  
D896 black wire.  
THERMOSTAT  
LIMIT  
CONTROLLER  
3
LIMIT  
CONTROLLER  
1
L1  
(HOT)  
2. Cycle the system through at least two appliance  
operations.  
L2  
TRANSFORMER  
DUAL AUTOMATIC  
VALVE COMBINATION  
GAS CONTROL  
1
2
TH TH  
Snap-Tite™ Connector Release  
To release the D896 cable from the knockout hole when  
secured with a Snap-Tite™ Box Connector (Fig.10), slip a  
screwdriver under the tab and twist.  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
2
3
CONNECT COLORS OF WIRING HARNESS AS SHOWN.  
M11372  
ALTERNATE LIMIT CONTROLLER HOOKUP.  
SETTINGS  
Fig. 8. Wiring diagram for D896 connection to continuous  
pilot system using wiring harness with one Molex plug.  
The service switch operates in both normal (NORM ) or  
service (SERV) modes. See Fig. 5.  
NORM—D896 opens on a call for heat and closes at the end  
of the heating cycle.  
SERV—D896 remains open at the end of a call for heat. The  
switch must be in the SERVICE position before manually  
opening the damper.  
D80B  
CABLE  
D892/D896  
CABLE  
YELLOW  
ORANGE  
YELLOW  
BLACK  
BLUE  
ORANGE  
BLUE  
RED  
BLACK  
OPERATION AND CHECKOUT  
D80B  
CONNECTOR  
M11383  
Operation  
On a call for heat, the CALL FOR HEAT LED on the actuator  
lights and the damper begins to open. When the damper is  
fully open, the IGNITION GAS PWR LED lights and the  
Fig. 9. Connecting D80B, D892 Cable to D896 Cable.  
7
68-0186  
 
D896 AUTOMATIC VENT DAMPER  
6. Cycle the heating system at least three times using the  
thermostat or controller to assure the system is  
operating safely.  
Cooling  
CAUTION  
Damage to air conditioner condenser possible.  
Do not operate cooling if outdoor temperature is below  
50°F (10°C).  
1. Set the thermostat or controller to COOL. Move the  
setpoint to 10°F (6°C) below the room temperature.  
2. Make sure the cooling system operates.  
3. Check that the D896 is in the closed position. See Fig.  
11.  
4. Return the thermostat or controller to the desired  
settings.  
NOTE TO INSTALLER: Explain to the homeowner that a  
yearly inspection by a trained, experienced service  
technician is necessary for safe, efficient operation  
of the vent damper and heating system. The  
homeowner should check for deterioration from  
corrosion or other sources between service  
technician calls.  
Fig. 10. Snap-Tite™ Box Connector release.  
Checkout  
Heating  
1. Turn on the power supply.  
2. If using a thermostat, set the heat anticipator at 0.13A.  
3. Set the thermostat or controller to 10°F (6°C) above the  
room temperature to call for heat.  
4. Check that the D896 CALL FOR HEAT and IGNITION  
GAS PWR LEDs light and that the damper opens  
before the gas valve opens and the pilot or main burner  
ignites. See Fig. 11.  
TROUBLESHOOTING  
WARNING  
Fire or explosion hazard can cause property  
damage, severe injury or death.  
NOTE: If a boiler gas control is sequenced by the  
Aquastat® Controller, make sure that the  
damper opens prior to the opening of the gas  
control.  
Explosion or carbon monoxide poisoning  
possible.  
Never apply a jumper across or short gas control  
terminals or wires because this can force the D896 to  
remain closed and cause an explosion.  
5. Turn the thermostat or controller 10°F (6°C) below the  
room temperature. Make sure the LEDs turn off and the  
D896 closes.  
THE AIR DUCT IS CLOSED WHEN THE  
INDICATOR POINTS PERPENDICULAR TO  
THE DIRECTION OF THE AIR DUCT  
THE AIR DUCT IS OPEN WHEN  
THE INDICATOR POINTS IN THE  
DIRECTION OF THE AIR DUCT  
M3431  
Fig. 11. Determining damper position.  
68-0186  
8
 
D896 AUTOMATIC VENT DAMPER  
NOTE: If there is a power failure, the damper remains  
exactly where it is at the moment of failure (open,  
closed or any position in between). When power is  
restored, the damper opens if the thermostat is  
calling for heat or closes if the thermostat is not  
calling for heat.  
heating contractor for repairs. The name of the original  
installer of your vent damper is on the installation label.  
Check vent damper operation as follows:  
1. Turn the thermostat or controller below the room  
temperature to turn off the furnace or boiler. Assure the  
vent damper position indicator points to the closed  
position. Refer to Fig. 11.  
If system fails to start, set the thermostat 10°F (6°C) below  
the room temperature for approximately three minutes, and  
refer to Table 2 to troubleshoot the system.  
2. Turn the thermostat or controller above the room  
temperature to call for heat. Assure the vent damper  
position indicator points to the open position. Refer to  
Fig. 11.  
3. Turn the thermostat or controller below the room  
temperature again. Assure the vent damper position  
indicator returns to the closed position.  
4. If the system has central air conditioning, set the  
thermostat or controller to COOL and turn it below the  
room temperature to call for cooling. Assure the cooling  
system operates with the vent damper in the closed  
position.  
INSTRUCTIONS TO THE HOMEOWNER  
A yearly inspection by a trained, experienced service  
technician is necessary for safe, efficient operation of the vent  
damper and all flue product-carrying areas of the appliance.  
The homeowner should check for deterioration from corrosion  
and other sources between service technician calls. If  
corrosion or other deterioration is noticed, contact your  
5. Return the thermostat or controller to the desired  
settings.  
Table 2.Troubleshooting.  
Possible Cause  
Thermostat Setting  
Symptom  
Action  
Set thermostat 10°F  
above room temperature  
to call for heat.  
No response from D896.  
Incorrect wiring or blown  
fuse.  
Check the circuit breaker or fuse and,  
if necessary, reset or replace.  
Check the transformer and limit  
control.  
Check for 24 Vac across resistor R1.  
Check for 24 Vac at the S8600, S8610  
and L8148E.  
Check wiring and cable connections.  
24 Vac is present, damper  
is open, CALL FOR HEAT  
LED is on, IGNITION GAS  
PWR LED is on, but no  
heat is produced.  
Appliance ignition  
system malfunction.  
Check appliance ignition system.  
24 Vac is present, damper  
is open, CALL FOR HEAT  
LED is on, IGNITION GAS  
PWR LED is off, no heat is  
produced.  
D896 malfunction.  
Replace the D896.  
24 Vac is present, damper  
Incorrect wiring or D896 Check all wiring and cable connections.  
is closed, CALL FOR HEAT malfunction.  
LED is off and no heat is  
produced.  
If 24 Vac is present across resistor  
R1, replace the D896.  
If 24 Vac is not present across R1,  
check the appliance ignition  
system.  
24 Vac is present, damper  
is closed and CALL FOR  
HEAT LED is off.  
Incorrect wiring or D896 Check all wiring and cable connections.  
malfunction.  
If 24 Vac is present across resistor  
R1, replace the D896.  
If 24 Vac is not present across R1,  
check the appliance ignition  
system.  
24 Vac is present, damper  
is closed and CALL FOR  
HEAT LED is on.  
Incorrect wiring or D896 If wiring is correct and the damper does  
malfunction.  
not fully open after approximately 30  
seconds, replace the D896.  
Set thermostat 10°F  
below the room  
temperature to end the  
call for heat.  
LEDs turn off, but damper  
does not close in  
approximately 30 seconds. malfunction.  
Incorrect service switch  
setting or D896  
Check if the service switch is in the  
normal (NORM ) position. If not, move  
the switch to the NORM position.  
If service switch is in the NORM  
position, replace the D896.  
9
 
68-0186  
D896 AUTOMATIC VENT DAMPER  
ANSI STANDARDS  
EXHIBIT A  
Procedure For Safety Inspection of an Existing Appliance Installation  
The following procedure is intended as a guide to aid in  
determining that an appliance is properly installed and is in a  
safe condition for continuing use.  
10. Determine that the pilot(s), when provided, is burning  
properly and that main burner ignition is satisfactory by  
interrupting and reestablishing the electrical supply to  
the appliance in any convenient manner.  
This procedure is predicated on central furnace, boiler and  
water heater installations, and it should be recognized that  
generalized procedures cannot anticipate all situations.  
Accordingly, in some cases deviation from this procedure may  
be necessary to determine safe operation of the equipment:  
a. This procedure shall be performed prior to installation  
of the automatic vent damper device.  
If the appliance is equipped with a continuous pilot(s), test the  
pilot safety device(s) to determine if it is operating properly by  
extinguishing the pilot(s) when the main burner(s) is off and  
determining, after 3 minutes, that the main burner gas does  
not flow upon a call for heat.  
b. If it is determined there is a condition which could result  
in unsafe operation, the appliance should be shut off  
and the owner advised of the unsafe condition. Do not  
install the automatic vent damper device until the  
unsafe condition has been corrected.  
If the appliance is not provided with a pilot(s), test for proper  
operation of the ignition system in accordance with the  
appliance manufacturer’s lighting and operating instructions.  
11. (a) Visually determine that main burner gas is burning  
properly; i.e., no floating, lifting or flashback. Adjust  
the primary air shutter(s) as required.  
(b) If the appliance is equipped with high and low  
flame controlling or flame modulation, check for  
proper main burner operation at low flame.  
12. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar or  
pipe.  
13. Turn on all other fuel-burning appliances within the  
same room so they will operate at their full inputs.  
Follow lighting instructions for each appliance.  
14. Repeat Steps 11 and 12 on the appliance being  
inspected.  
15. Return doors, windows, exhaust fans, fireplace  
dampers and any other fuel-gas burning appliances to  
their previous conditions of use.  
The following steps are to be followed in making the safety  
inspection:  
1. Conduct a gas leakage test of the appliance piping and  
control system downstream of the shutoff valve in the  
supply line to the appliance.  
2. Visually inspect the venting system for proper size,  
horizontal pitch and vent termination, and determine  
there is no blockage or restriction, leakage, corrosion  
and other deficiencies which could cause an unsafe  
condition.  
3. Determine that the chimney or vent is acceptable to the  
authority having jurisdiction.  
4. Shut off all gas to the appliance and shut off any other  
fuel-gas burning appliance within the same room. Use  
the shutoff valve in the supply line to each appliance.  
5. Inspect burners and crossovers for blockage and  
corrosion.  
16. Applicable only to furnaces—Check both the limit  
control and the fan control for proper operation. Limit  
control operation can be checked by blocking the  
circulating air inlet or temporarily disconnecting the  
electrical supply to the blower motor and determining  
that the limit control acts to shut off the main burner  
gas.  
6. Applicable only to furnaces—inspect heat exchanger for  
cracks, openings or excessive corrosion.  
7. Applicable only to boilers—inspect for evidence of water  
or combustion product leaks.  
8. Insofar as is practical, close all building doors and  
windows and all doors between the space in which the  
appliance is located and other spaces of the building.  
Turn on clothes dryers. Turn on any exhaust fans, such  
as range hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers. If, after  
completing Steps 9 through 14, it is believed sufficient  
combustion air is not available, refer to local codes, or  
in the absence of local codes, to the National Fuel Gas  
Code, ANSI Z223.1-1988 (NFPA 54), for guidance.  
9. Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat so  
appliance will operate continuously.  
17. Applicable only to boilers—  
(a) Determine that the water pumps are in operating  
condition.  
(b) Test low water cutoffs, automatic feed controls,  
pressure and temperature limit controls, and relief  
valves in accordance with the manufacturer’s  
recommendations to determine they are in  
operating condition.  
Exhibit A of ANSI Standard Z21.66-1994 for Electrically Operated Automatic Vent Damper Devices  
for use with Gas-Fired Appliances.  
68-0186  
10  
 
D896 AUTOMATIC VENT DAMPER  
EXHIBIT B  
Procedure for Installing Electrically Operated Automatic Vent Damper Devices on Existing Appliances  
This procedure is intended as a guide to aid in safely  
installing an electrically operated or mechanically actuated  
automatic vent damper device on an existing appliance.  
10. Insofar as is practical, close all building doors and  
windows and all doors between the space in which the  
appliance is located and other spaces of the building.  
Turn on clothes dryers. Turn on any exhaust fans, such  
as range hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
This procedure is based on the assumption that the history of  
the specific appliance has been one of safe and satisfactory  
operation.  
11. Place appliance in operation. Follow the lighting  
instructions. Adjust thermostat so appliance will operate  
continuously.  
12. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar or  
pipe.  
13. (a) Visually determine that main burner gas is burning  
properly; i.e., no floating, lifting or flashback. Adjust  
the primary air shutter(s) as required.  
This procedure is predicated on central furnace, boiler and  
water heater installations, and it should be recognized that  
generalized procedures cannot anticipate all situations.  
Accordingly, in some cases deviation from this procedure may  
be necessary to determine safe operation of the equipment.  
The following steps are to be followed in making the  
modifications:  
1. Perform a safety inspection of the existing appliance  
installation. See Exhibit A for the recommended  
procedure for such a safety inspection.  
2. Shut off all gas and electricity to the appliance. To shut  
off gas use the shutoff valve in the supply line to the  
appliance.  
3. Install the automatic vent damper device in strict  
accordance with the manufacturer’s installation  
instructions. Make certain the device is not located in  
that portion of the venting system which serves any  
appliance other than the one for which the damper is  
installed.  
(b) If the appliance is equipped with high and low  
flame controlling or flame modulation, check for  
proper main burner operation at low flame.  
14. Determine that the pilot(s), when provided, is burning  
properly and that main burner ignition is satisfactory by  
interrupting and reestablishing the electrical supply to  
the appliance in any convenient manner.  
If the appliance is equipped with a continuous pilot(s), test the  
pilot safety device(s) to determine if it is operating properly by  
extinguishing the pilot(s) when the main burner(s) is off and  
determining, after 3 minutes, that the main burner gas does  
not flow upon a call for heat.  
4. Make certain wiring connections are tight and wires are  
positioned and secured so they will not be able to  
contact high temperature locations.  
5. When an additional automatic valve has been  
incorporated or an existing gas control replaced,  
conduct a gas leakage test of the appliance piping and  
control system downstream of the shutoff valve in the  
supply line to the appliance.  
If the appliance is not provided with a pilot(s), test for proper  
operation of the ignition system in accordance with the  
appliance manufacturer’s lighting and operating instructions.  
15. Applicable only to furnaces—Check both the limit  
control and the fan control for proper operation. Limit  
control operation can be checked by blocking the  
circulating air inlet or temporarily disconnecting the  
electrical supply to the blower motor and determining  
that the limit control acts to shut off the main burner  
gas.  
6. Visually inspect the modified venting system for proper  
horizontal pitch.  
7. Check that the damper and gas valve(s) are in the  
correct operating sequence.  
(a) The damper must be in the full open position  
before the gas valve(s) opens.  
(b) The damper must remain in the full open position  
while the gas valve(s) is open.  
(c) The gas valve(s) must be closed before damper  
begins its return to the closed position.  
(d) The damper shall remain in the closed position  
during the off cycle of the appliance.  
16. Applicable only to boilers—  
(a) Determine that the water pumps are in operating  
condition.  
(b) Test low water cutoffs, automatic feed controls,  
pressure and temperature limit controls, and relief  
valves in accordance with the manufacturer’s  
recommendations to determine they are in  
operating condition.  
8. Determine the amperage draw of the gas control circuit  
and damper device.  
(a) Check appliance transformer for adequate  
capacity.  
17. Label the damper device (see 1.7.5) with information as  
to:  
(b) Check heat anticipator in comfort thermostat to  
determine if it is properly adjusted.  
9. Sequence the appliance through at least three normal  
operating cycles.  
(a) Name of qualified agency responsible for damper  
installation.  
(b) Date of installation.  
Exhibit B of ANSI Standard Z21.66-1994 for Electrically Operated Automatic Vent Damper Device  
for use with Gas-Fired Appliances.  
11  
68-0186  
 
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis MN 55408-0524  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
Honeywell Asia Pacific Inc.  
Room 3213-3225  
Sun Hung Kai Centre  
No. 30 Harbour Road  
Wanchai  
M2H 2C9  
Hong Kong  
Honeywell Europe S.A.  
3 Avenue du Bourget  
Honeywell Latin American Division  
Miami Lakes Headquarters  
B-1140 Brussels Belgium  
14505 Commerce Way Suite 500  
Miami Lakes FL 33016  
Helping You Control Your World®  
68-0186 J.S. 3-97 Printed in U.S.A.  
customer.honeywell.com  
 

Grundig CRT Television LXW 68 9620 User Manual
Haier Washer Dryer HWM50 10 User Manual
Hasbro Motorized Toy Car 87953 User Manual
Honeywell Cooktop Central Heating Cooker Natural Gas User Manual
Honeywell Thermostat Y594 User Manual
Hotpoint Washer Dryer WMA10 User Manual
Hotpoint Washer WML 520 P G A K User Manual
HP Hewlett Packard Ventilation Hood HP 83006A User Manual
Hyundai Car Satellite TV System H CDM8010 User Manual
iHome MP3 Docking Station iH3 User Manual